Screw-in resistance thermometer without extension pipe

To the configurator

Screw-in resistance thermometer without extension pipe

Fitting with replaceable resistance thermometer inset

Calculation of the inset length = Nominal length + 45mm

TEMPERATURE LOAD
OPERATING CONDITIONS

Structure of the fitting:

Protective tube diameter 6 – 14 mm and screw neck G½“ connection head made of light metal Form B according to DIN EN 50446 with cable entry M20x1.5.
(For variants please refer to the worksheet).

Structure of the inset in accordance with DIN 43735:

Precision resistor single or dual, Type Pt-100. Basic values as per IEC 60751 in Tolerance class B or A. Connected in 2-, 3- or 4-wire circuit from precision resistor, installed in a rigid inset pipe of stainless steel material or as sheath resistance thermometer inset in flexible version with a diameter of 6 mm. Shelf plate with connection socket.
(For variants please refer to the worksheet).

Types of wiring: